Design Criteria: Commercial

Please See Guide: Design Criteria for Commercial Construction in the City of Twin Falls


  • Wind Exposure
    • “B” (“C” in some areas)
  • Roof Snow Load
    • Section 1608 
      • amended to include that the minimum uniformly distributed design load shall be 25psf (lbs./ft2). 
    • Table 1607.1 
      • amended to require a minimum uniform live load of 40psf (lbs./ft2) in habitable attics and sleeping rooms
  • Frost Depth for Footing Protection
    • 24 inches
  • Presumed Soil Bearing Pressure
    • 1500psf (lbs./ft2) for “allowable stress design” 
    • Others to comply with 2018 IBC Chapter 16 
  • Climate Zone
    • 5B