Links to design criteria are available at the bottom of the webpage.
2017 National Electrical Code (with Idaho State amendments)
2017 Idaho State Plumbing Code [website]
2018 International Building Code (with Idaho State amendments)
2018 International Fire Code [website]
2018 International Existing Building Code
2018 International Energy Conservation Code (with Idaho State amendments)
2018 International Mechanical Code (with Idaho State amendments)
2018 International Fuel Gas Code (with Idaho State amendments
2009 ICC A117.1-2009 Accessible and Usable Buildings and Facilities
1997 Uniform Code for the Abatement of Dangerous Buildings (per local ordinance)
Wind speed: Designed per section 1609 of 2018 IBC (Vult=(105 mph) Category I, (115mph) Category II, and (120 mph) Category III and IV)
Wind exposure: “B” (“C” in some areas)
Ground Snow Load: 15 psf
Roof Snow Load: per IBC, but Section 1608 is amended to include that the minimum uniformly distributed design load shall be 25 psf. Table 1607.1 is amended to require a minimum uniform live load of 40 psf in habitable attics and sleeping rooms
Seismic Criteria: Per section 1613 of IBC [website]
Frost Depth: 24 inches
Presumed soil bearing pressure: 1500psf for “allowable stress design”; others to comply with Chapter 16
Climate Zone: 5B